Shinko Technos SE2EA-1-0-0 Manuel d'instructions Page 1

Naviguer en ligne ou télécharger Manuel d'instructions pour Systèmes de contrôle d'accès de sécurité Shinko Technos SE2EA-1-0-0. Shinko Technos SE2EA-1-0-0 Instruction manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - SE A SERIES

PLUG-IN TYPEALARM DETECTORSE A SERIESINSTRUCTION MANUAL

Page 2

- 10 -(2) Confirm that the Lock Release is lowered.(Fig. 3.2-2)(3) Insert the SE A series into the socket.(Fig. 3.2-3)When inserting, be carefulabout

Page 3

- 11 -(4) Fix the SE A series and the socket by pushing the Lock Release up.(Fig. 3.2-4)3.3. Removal from a DIN Rail(1) Turn the power supply to the u

Page 4 - Model Explanation

- 12 -(3) Separate the SE A series from the socket.(Fig. 3.3-2)(4) Remove the socket from the DIN rail by pulling the Socket Lock Release (at thebotto

Page 5 - CONTENTS

- 13 -4. WiringWarningTurn the power supply to the instrument off before wiring.Working on or touching the terminal with the power switched on may res

Page 6 - 1. Model

- 14 -1234-+5678-+CH1CPU13149101112-+-+-+CH2inputcircuitCH1inputcircuitInsulationcircuitInsulationcircuitInsulationcircuitInsulationcircuitDisplay/Set

Page 7

- 15 -1234+-5678+-CPU13149101112-+-+-+Power supplyCH1A2outputCH2A2outputCH1A3outputCH2A3outputCH2outputcircuitPowercircuitDisplay/Settingkey circuitIn

Page 8

- 16 -1234-+5678CH1CPU13149101112-+-+-+A1 outputA2 outputA3outputA4outputA5outputA6outputInputcircuitPowercircuitOutputcircuitOutputcircuitInsulationc

Page 9 - 3. Mounting

- 17 -1234+-5678CPU13149101112-+-+-+A1 outputA2 outputCH1A3outputA4outputA5outputA6outputInputcircuitPowercircuitOutputcircuitOutputcircuitInsulationc

Page 10

- 18 -910ACLoadInductive load (coil)Varistor, CR circuit, etc.910DCLoadDiode, varistor,CR circuit, etc.Inductive load (coil)4.3 Wiring of TerminalsWar

Page 11

- 19 -Output specifications are shown below.Open collector Control capacity: 0.1 A 24 V DCAlarm output wiring example(Fig. 4.3.2-3)4.3.3 Input WiringC

Page 12

- 2 -PrefaceThank you for purchasing the SE A series Alarm Detector. This manual containsinstructions for the mounting, functions, operations and note

Page 13 - 4. Wiring

- 20 -5. Key Operation FlowchartSE2 APOWER ONRUN ModeCH1 CH2 CH1Alarm Setting GroupAlarm Setting GroupFunction GroupA1 value A1 value Input rangeScali

Page 14

- 21 -CH2 Special FunctionFunction Group GroupA1 Energized/De-energized Setting items: Same as Set value lock: Energized CH1 function group. : Unlock:

Page 15 - V( 1V) DC

- 22 -SE1 APOWER ONRUN ModeAlarm setting Function GroupgroupA1 value A4 value Input rangeScaling low limit to Scaling low limit to See (Table 5-3).Sca

Page 16 - (Fig. 4.2-6)

- 23 -Special FunctionGroupA6 type A5 HOLD function Set value lockSee (Table 5-4). : OFF : Unlock: ON : Lock 1A1 Energized/De-energized : Lock 2: Ener

Page 17

- 24 -6. SetupSetup should occur before using this unit, to set (or select) an Input range, Scaling low limitvalue, Scaling high limit value, Alarm ty

Page 18

- 25 -(Table 6-2) SE1 ASetting Item Factory Default ValueK -200 to 1370 (SE1EA)Pt100 -200 to 850 (SE1RA)4 to 20 mA DC -1999 to 9999 (SE1AA)Input range

Page 19

- 26 -Setting Item Factory Default ValueA1 delay timeA2 delay timeA3 delay timeA4 delay timeA5 delay timeA6 delay time0 secSpecial function group (Com

Page 20 - 5. Key Operation Flowchart

- 27 -6.1 Indication after Power-onAfter power-on, the unit moves to warm-up status for approx. 3 seconds as shown belowin (Fig. 6.1-1) and (Fig. 6.1-

Page 21 - A2 Energized/De-energized

- 28 -After that, the unit switches to RUN mode as shown below in (Fig. 6.1-3), (Fig. 6.1-4).SE2 A(Fig. 6.1-3)SE1 A(Fig. 6.1-4)6.2 Basic Operation of

Page 22

- 29 -SetvalueInputvalue(1) RUN Mode(Fig. 6.2-1)(2) CH1 Function Group(Fig. 6.2-2)(3) Input Range Selection(Fig. 6.2-3)To set (or select)each item, us

Page 23 - Special Function

- 3 -11..IInnssttaallllaattiioonnPPrreeccaauuttiioonnssCautionThis instrument is intended to be used under the following environmental conditions(IEC6

Page 24 - 6. Setup

- 30 -6.3 Setup6.3.1 Function GroupFor the SE2 A, this is the function group for CH1.To enter the function group, follow the procedures below.(1) Pres

Page 25

- 31 -Display Name, Function, Setting Range Factory Default ValueInput range (SE2RA, SE1RA) Pt100 -200 to 850• For the SE2RA and SE1RA, selects a RTD

Page 26

- 32 -Display Name, Function, Setting Range Factory Default ValueScaling high limit 1370 (SE2EA, SE1EA)850 (SE2RA, SE1RA)9999 (SE2AA, SE2VA, SE1AA, SE

Page 27

- 33 -Display Name, Function, Setting Range Factory Default ValueA1 type No alarm actionINOUT• Selects an A1 type.Note: If an A1 type is changed, the

Page 28

- 34 -Display Name, Function, Setting Range Factory Default ValueA2 type No alarm actionINOUT• Selects an A2 type.Available for 6 points alarm output

Page 29

- 35 -Display Name, Function, Setting Range Factory Default ValueA5 type No alarm actionINOUT• Selects an A5 type.Available for 6 points alarm output

Page 30

- 36 -Display Name, Function, Setting Range Factory Default ValueA4 Energized/De-energized EnergizedINOUT• Selects A4 action Energized or De-energized

Page 31

- 37 -Display Name, Function, Setting Range Factory Default ValueA4 HOLD function OFFINOUT• Selects OFF or ON for A4 HOLD function.If alarm HOLD is se

Page 32

- 38 -Display Name, Function, Setting Range Factory Default ValueA3 hysteresis 1.0 (SE2EA, SE2RA, SE1EA, SE1RA)1.0% (SE2AA, SE2VA, SE1AA, SE1VA)INOUT•

Page 33

- 39 -Display Name, Function, Setting Range Factory Default ValueA2 delay time 0 secINOUT• Sets A2 action delay time.A2 output does not turn ON until

Page 34

- 4 -Model ExplanationModel names included in this manual are indicated below.Name ModelSE2 A SE2EA, SE2RA, SE2AA, SE2VASE A seriesSE1 A SE1EA, SE1RA,

Page 35

- 40 -6.3.2 CH2 Function GroupAvailable only for the SE2 A.To enter the CH2 Function Group, follow the procedures below.(1) In the RUN mode, press the

Page 36

- 41 -Display Name, Function, Setting Range Factory Default ValueDisplay selection CH1 input value/A1 value (SE2 A)Input value /A1 value (SE1 A)INOUT•

Page 37

- 42 -SetvalueInputvalue7. Alarm Settings7.1 Basic Operation of Alarm SettingsAlarm settings are conducted in the Alarm setting groups.For the SE2□A,

Page 38

- 43 -(2) Alarm Setting Group(Fig. 7.1-2)(3) A1 Value(Fig. 7.1-3)Press the key while theAlarm setting group charactersare being indicated.Please useth

Page 39

- 44 -7.2 Alarm Settings7.2.1 Alarm Setting GroupFor the SE2 A, this is the alarm setting group for CH1.To enter the Alarm setting group, follow the p

Page 40

- 45 -7.2.2 CH2 Alarm Setting GroupAvailable only for the SE2 A.To enter the CH2 alarm setting group, follow the procedures below.(1) In the RUN mode,

Page 41

- 46 -8. Operation8.1 Indication after Power-onAfter power-on, the unit moves to warm-up status for 3 seconds as shown belowin (Fig. 8.1-1) and (Fig.

Page 42 - 7. Alarm Settings

- 47 -(Table 8.1-1)Input DisplayInputKKJRSBETNPL-W5Re/W26ReW3Re/W25Re: -200 to 1370: 0 to 400: -200 to 1000: -50 to 1760: -50 to 1760: 0 to 1820: -200

Page 43

- 48 -SetvalueInputvalueSetvalueInputvalue8.2 Unit OperationThe unit enters the RUN mode after 3-second warm-up indication as shown in(Fig. 8.2-1) and

Page 44

- 49 -• Indication when Alarm Output is ONSE2 A:When alarm output is ON, the relevant channel indicator with current alarm outputON will flash, and th

Page 45

- 5 ---- CONTENTS ---1. Model Page1.1 Model ---------------------------------------------------------------------------- 61.2 How to Read the Model La

Page 46 - 8. Operation

- 50 -• Indication when input value is -200.0 (-2000) or lessWhen the range has a decimal point: For the indication of -200.0 or less, the input value

Page 47

- 51 -9. SpecificationsInput SpecificationsSE2EA, SE1EA Input resistance: 1 M or moreExternal resistance: 100 or less, However, B: 40 or lessBurnout:

Page 48

- 52 -Output SpecificationsSE2 A: Up to 3 points alarm output for each channel can beselected.SE1 A: Up to 6 points alarm output can be selected.For e

Page 49

- 53 -PerformanceReference inputaccuracy (at 23 )SE2EA and SE1EA:Within 0.1% of each input spanR, S inputs -50 to 200 (-58 to 392 ): Within 6 (12 )B i

Page 50

- 54 -10. Troubleshooting10.1 IndicationProblem Presumed Cause and SolutionThe Input display isflashing " " or" ".The input value

Page 51 - 9. Specifications

- 55 -11. Character TableAlarm Setting GroupSE2 A: CH1 and CH2 have respective setting items.Display Setting Item Factory Default Value DataA1 valueA2

Page 52

Display Setting Item Factory Default Value DataA5 HOLD functionA6 HOLD functionOFFA1 hysteresisA2 hysteresisA3 hysteresis1.0 (SE2EA, SE2RA, SE1EA, SE1

Page 53 - Ambient temperature -5 to 55

- 6 -1. Model1.1 ModelSE A SeriesS E A- -2 E 2ch alarm detector (thermocouple)2 R 2ch alarm detector (RTD)2 A 2ch alarm detector (direct current) (*)2

Page 54 - 10. Troubleshooting

- 7 -1.2 How to Read the Model LabelThe model label is attached to the left side of the case.SE2 AModel (E.g. SE2EA-1-0-0)CH1 input (Enter a range sel

Page 55 - 11. Character Table

- 8 -2. Name and Functions of SectionsSE2 ASE1 A(Fig. 2-2)NoticeWhen setting the specifications and functions of this instrument, connect terminals 13

Page 56 - SHINKO TECHNOS CO., LTD

- 9 -3. Mounting3.1 External Dimensions (Scale: mm)(Fig. 3.1-1)3.2 Mounting to a DIN Rail(1) Hook the upper part of the socket on the DIN rail, and mo

Commentaires sur ces manuels

Pas de commentaire