- 6 -
1. Model
1.1 Model
SE A Series
S E A- -
2 E 2ch alarm detector (thermocouple)
2 R 2ch alarm detector (RTD)
2 A 2ch alarm detector (direct current) (*)
2ch
alarm
detector
2 V 2ch alarm detector (DC voltage)
1 E 1ch alarm detector (thermocouple)
1 R 1ch alarm detector (RTD)
1 A 1ch alarm detector (direct current) (*)
1ch
alarm
detector
1 V 1ch alarm detector (DC voltage)
1
Screw fall prevention, Finger-safe
(For Y terminal)Socket
2 For Ring terminal
0 100 to 240 V AC
Power supply
1 24 V AC/DC
0
2
points
SE2 A: 1 alarm output for each
channel
SE1 A: 2 alarm outputs
Output points
1
6
points
SE2 A: 3 alarm outputs for each
channel
SE1 A: 6 alarm outputs
(*) For direct current input, a shunt resistor (sold separately) is required.
(E.g.) SE2EA-1-0-0
Alarm detector type: 2ch alarm detector (thermocouple)
Socket: Screw fall prevention, Finger-safe (For Y terminal)
Power supply: 100 to 240 V AC
Output points: 2 points (1 alarm output for each channel)
Factory default value: CH1 input: K -200 to 1370
CH2 input: K -200 to 1370